Third-harmonic generator manual
three harmonic generator Introduction
According to the national test standards for power transformers and voltage transformers induction test voltage roughly 2-3 times the maximum working phase voltage considerations. As we all know, the transformer at rated frequency, rated voltage, the core approaches saturation, if the employment test frequency power transformer windings being greater than the rated voltage is applied across the test voltage, the load excitation current to increase dramatically, reaching levels not be allowed , from the relationship between the EMF can be seen that in order to apply the test voltage is greater than the rated voltage, which does not saturate the iron core, the method can be used to increase the power frequency, power supply must be greater than the frequency generator.
Use
BYSBF five columns with three-core structure, the magnetic flux density of the core work in the saturation flux density above selection, the opening connected to the secondary winding of a triangle in the fundamental electrical potential (positive sequence vector) vector and a is 0, and two openings terminal should be the same phase 150Hz third harmonic (zero sequence).
Product Features
Simple operation, reliable performance, can satisfy transformers, inductive voltage transformer needs.
Use of the environment
1, Power requirements: Three-phase 380V/50Hz
Third-harmonic generator
2, ambient temperature: -25 ℃ - 55 ℃
3 Altitude: not more than 4000 m
4, for voltage transformers, motors, transformers, AC induction voltage test to assess the master-slave dielectric strength, but also for short-run 150Hz power supply.
5, the input voltage: AC380V50Hz
6, the output voltage: 300V-500V (available on request 0-5kV) voltage> 300V devices require an external boost
7, the waveform distortion: <5%
8, the output capacity: 3kVA-150kVA
Technical parameters
1 Power supply: three-phase AC 380V ± 10% 50Hz
2, rated capacity: 3KVA-30KVA (for selection)
3, the output voltage :50-500V (max 750V), 150Hz 100-1000V (max 1500V), 150Hz
4, capacity :1-1000KVA
5, waveform: sine, distortion less than 1%
6, load: resistive, inductive, capacitive available
Technical Specifications
Input voltage 380V 50Hz sine wave
Output voltage 250V-1000V 150Hz waveform distortion ≤ 5%
Output capacity 3kVA, 5kVA, 10kVA, 20kVA, 50kVA
No-load running time ≤ 5分鐘